Dry-type Transformer
Level 2 Energy Efficiency Dry-type Power Transformer

Details
MEDIUM VOLTAGE DRY-TYPE TRANSFORMER
TECHNICAL DATASHEET
- General Information
- Product: Medium Voltage Dry-Type Power Transformer
- Type: Distribution Transformer
- Cooling Method: Air Natural (AN) / Air Forced (AF)
- Installation: Indoor / Outdoor (enclosure type for outdoor)
- Applicable Standards: IEC 60076, IEEE C57, EN 50588
- Ratings
| Item | Description |
| Rated Power | 50 kVA – 2500 kVA (up to 5000 kVA on request) |
| Rated Frequency | 50 Hz / 60 Hz |
| Number of Phases | Three-phase |
| Vector Group | Dyn11 (other options available upon request) |
| Duty Type | Continuous |
| Insulation Class | F or H (temperature rise 115°C / 150°C) |
- Rated Voltages
| Side | Voltage |
| High Voltage (HV) | 6 / 10 / 11 / 13.8 / 20 / 22 / 33 kV |
| Low Voltage (LV) | 0.4 / 0.415 / 0.48 / 0.69 kV |
| Highest Voltage for Equipment | Up to 36 kV |
- Tap Changer
- Type: Off-circuit tap changer (OC)
- Tapping Range: ±2 × 2.5% (or ±5%)
- Location: HV side
- On-load Tap Changer (OLTC): Optional (mainly for industrial applications)
- Insulation & Dielectric Strength
- Winding Insulation: Class F or H, vacuum-impregnated resin (VPI)
- Creepage Distance: According to IEC 60076
- Lightning Impulse Withstand (BIL): As per IEC 60076 standard for MV dry-type transformers
- Temperature Rise
| Item | Limit |
| Winding Temperature Rise | ≤ 115°C (Class F) / ≤ 150°C (Class H) |
| Ambient Temperature | Max. 40°C, Min. −25°C |
| Relative Humidity | ≤ 95% |
- Losses and Efficiency
- No-load Loss: According to IEC 60076
- Load Loss: According to IEC 60076
- Efficiency: High-efficiency, low-loss design
- Sound Level: ≤ 55 dB (depending on size and standard)
- Construction Details
- Core: Cold-rolled, grain-oriented silicon steel
- Windings: Copper (Aluminum optional)
- Insulation: Vacuum-impregnated epoxy resin (VPI)
- Enclosure: Sheet steel or IP-rated box for outdoor installation
- Finish: Powder coating or RAL color as requested
- Standard Accessories
- Temperature indicator (thermometer / PT100 optional)
- Pressure relief vent (for enclosed type)
- Lifting lugs / earthing terminals
- Nameplate / Rating plate
- Optional: Monitoring devices, external cooling fans
- Tests
Routine Tests (IEC 60076):
- Winding resistance measurement
- Ratio and vector group verification
- No-load loss and current
- Load loss and impedance
- Insulation tests
Type / Special Tests (Optional):
- Temperature rise test
- Noise level measurement
- Partial discharge test
- Service Conditions
- Installation altitude: ≤ 1000 m
- Ambient temperature: −25°C to +40°C (customizable)
- Relative humidity: ≤ 95%
- Pollution degree: PD2 (IEC 60076-11)
- Applications
- Indoor and outdoor distribution networks
- Industrial plants
- Commercial buildings
- Renewable energy systems (solar, wind)
- Data centers and critical power facilities
- Compliance Statement
The medium voltage dry-type transformer is designed, manufactured, and tested in accordance with IEC 60076, IEEE C57, and relevant international standards. It provides reliable operation, high efficiency, and safe performance for utility, industrial, and commercial applications.
📌 Notes
- For export, clearly specify Rated Voltagevs Highest Voltage for Equipment
- Vector group Dyn11 is widely used for industrial and commercial networks
- Outdoor installations should use enclosed or IP-rated type
- Can be customized for higher temperature class (H), larger kVA, or specific monitoring devices
-