wordpress

Professional Transformer Manufacturer & Supplier
500kV 500kV
Ultra-high voltage transformer

500kV

500kV
Details

ULTRA HIGH VOLTAGE (UHV) POWER TRANSFORMER

TECHNICAL DATASHEET

  1. General Information
    • Product Name: Ultra High Voltage Power Transformer
    • Transformer Type: Oil-Immersed Power Transformer
    • Application: Long-distance bulk power transmission, UHV substations
    • Installation: Outdoor
    • Cooling Method: ONAN / ONAF / OFAF / OFWF
    • Phases: Single-phase or Three-phase
    • Frequency: 50 Hz / 60 Hz
    • Standards:
  • IEC 60076 Series
  • IEC 60076-1 / 60076-3 / 60076-5
  • IEEE C57 (upon request)
  • GB/T 1094 (China)
  1. Rated Data
ParameterSpecification
Rated Power500 MVA – 1500 MVA (customizable)
Highest Voltage for Equipment1000 kV AC / ±800 kV DC / ±1100 kV DC
Rated Voltage (HV)1000 kV / ±800 kV / ±1100 kV
Rated Voltage (LV / MV)500 kV / 400 kV / 220 kV
Rated CurrentAccording to rated power and voltage
Vector GroupYNyn0 / YNyn0d11 / customer specified
Tap ChangerOLTC (On-Load Tap Changer)
Tapping Range±10% or as specified
Tapping Step1.25% / 1.5%
  1. Electrical Characteristics
    • Short-Circuit Impedance: 12% – 30% (customizable)
    • Short-Time Withstand Current: According to IEC 60076-5
    • Insulation Level:
  • Lightning Impulse Withstand Voltage (LIWV): Up to 3000 kV
  • Switching Impulse Withstand Voltage (SIWV): According to UHV standards
    • Partial Discharge Level: ≤ 100 pC
    • No-Load Loss: Optimized low-loss core design
    • Load Loss: According to IEC / project specifications
  1. Insulation System
  • Insulation Medium: Mineral oil / Natural ester oil (optional)
  • Solid Insulation: High-density cellulose paper & pressboard
  • Insulation Structure: Oil-paper composite insulation system
  • Bushing Type: Oil-Impregnated Paper (OIP) / Resin-Impregnated Paper (RIP)
  • Creepage Distance: Designed according to pollution level (IEC 60815)
  1. Core & Windings
  • Core Material: High-permeability grain-oriented silicon steel
  • Core Type: Five-limb or multi-limb core structure
  • Windings: Continuously transposed copper conductors (CTC)
  • Mechanical Strength: Designed to withstand extreme short-circuit forces
  • Shielding: Electrostatic and magnetic shielding to reduce losses and hotspots
  1. Cooling System
  • Cooling Modes:
  • ONAN – Oil Natural / Air Natural
  • ONAF – Oil Natural / Air Forced
  • OFAF – Oil Forced / Air Forced
  • OFWF – Oil Forced / Water Forced
    • Radiators: Detachable radiator banks
    • Oil Pumps & Fans: Redundant configuration for high reliability
    • Temperature Rise: According to IEC 60076 limits
  1. Tank & Mechanical Design
  • Main Tank: Welded steel structure with reinforced mechanical strength
  • Conservator: Diaphragm or bladder type oil conservator
  • Surface Treatment: Sand blasting + anti-corrosion painting system
  • Color: RAL customizable
  • Seismic Design: Optional, according to IEEE / IEC seismic requirements
  1. Monitoring & Protection
  • Oil temperature indicators (OTI / WTI)
  • Online dissolved gas analysis (DGA) – optional
  • Buchholz relay
  • Pressure relief device
  • Oil level indicator
  • Online bushing monitoring system – optional
  • Fiber optic temperature monitoring – optional
  1. Tests

Routine Tests

  • Winding resistance measurement
  • Voltage ratio and phase displacement
  • Insulation resistance and dielectric tests
  • No-load and load loss measurement

Type Tests

  • Temperature rise test
  • Lightning impulse test
  • Switching impulse test
  • Short-circuit withstand test
  • Partial discharge measurement

Special Tests (Optional)

  • Sound level test
  • Zero-sequence impedance test
  • Seismic test
  1. Environmental Conditions
  • Ambient Temperature:
  • Maximum: +40°C
  • Minimum: −25°C (lower on request)
    • Altitude: ≤ 1000 m above sea level
    • Pollution Level: Light / Medium / Heavy (as per IEC 60815)
    • Installation: Outdoor, UHV substation
  1. Typical Applications
  • Ultra High Voltage AC transmission systems (1000 kV)
  • UHV DC converter stations (±800 kV / ±1100 kV)
  • Long-distance bulk power transmission
  • National grid backbone networks
  1. Compliance & Certification

This Ultra High Voltage Power Transformer is designed, manufactured, and tested in full compliance with IEC 60076 series, GB/T 1094, and relevant IEEE standards, ensuring reliable operation in UHV transmission networks worldwide.

  1. Customization Options
  • Rated voltage and power tailored to project requirements
  • Ester oil for enhanced fire safety and environmental protection
  • High seismic resistance design
  • Advanced online monitoring systems
  • Special insulation design for extreme pollution or altitude

Summary

The Ultra High Voltage Power Transformer is a critical component of modern bulk power transmission systems. Designed for maximum reliability, ultra-low losses, and long service life, it meets the stringent requirements of UHV AC and DC transmission projects worldwide.

 

DATA DOWNLOAD
  • I have read and agree to the Privacy Policy.
E-mail WhatsApp