wordpress

Professional Transformer Manufacturer & Supplier
35kV-class Power Transformer 35kV-class Power Transformer
Oil-immersed transformer

35kV-class Power Transformer

35kV-class Power Transformer
Details

MEDIUM VOLTAGE OIL-IMMERSED TRANSFORMER

TECHNICAL DATASHEET

  1. General Information
    • Product: Medium Voltage Oil-Immersed Power Transformer
    • Type: Distribution Transformer
    • Cooling Method: ONAN (Oil Natural Air Natural)
    • Installation: Outdoor / Indoor
    • Applicable Standards: IEC 60076
  1. Ratings
ItemDescription
Rated Power50 kVA – 2500 kVA (up to 5000 kVA on request)
Rated Frequency50 Hz / 60 Hz
Number of PhasesThree-phase
Vector GroupDyn11 (others available upon request)
Cooling TypeONAN
Duty TypeContinuous
  1. Rated Voltages
SideVoltage
High Voltage (HV)6 / 10 / 11 / 13.8 / 20 / 22 / 33 kV
Low Voltage (LV)0.4 / 0.415 / 0.48 / 0.69 kV
Highest Voltage for EquipmentUp to 36 kV
  1. Tap Changer
  • Type: Off-circuit tap changer
  • Tapping Range: ±2 × 2.5% (or ±5%)
  • Location: HV side
  • On-load Tap Changer (OLTC): Optional
  1. Insulation Levels
Highest VoltagePower Frequency WithstandLightning Impulse Withstand (BIL)
12 kV28 kV75 kV
24 kV50 kV125 kV
36 kV70 kV170 kV
  1. Temperature Rise
ItemLimit
Winding Temperature Rise≤ 65 K
Top Oil Temperature Rise≤ 60 K
Ambient TemperatureMax. 40°C
  1. Losses and Efficiency
  • No-load Loss: According to IEC 60076
  • Load Loss: According to IEC 60076
  • Efficiency: High efficiency, low loss design
  • Sound Level: In compliance with IEC limits
  1. Insulating Oil
  • Type: Mineral Insulating Oil
  • Standard: IEC 60296
  • Optional: Natural Ester Oil (FR3)
  1. Construction Details
  • Core:
    Cold-rolled grain-oriented silicon steel, step-lap construction
  • Windings:
    Copper (Aluminum optional upon request)
  • Tank:
    Welded steel tank, corrosion-resistant coating
  • Finish:
    Outdoor anti-corrosion paint, RAL color optional
  1. Accessories (Standard)
  • Conservator
  • Oil level indicator
  • Temperature indicator
  • Pressure relief device
  • Earthing terminals
  • Rating plate (stainless steel)
  1. Tests

Routine Tests (IEC 60076):

  • Measurement of winding resistance
  • Ratio and vector group verification
  • No-load loss and current
  • Load loss and impedance
  • Insulation tests

Type / Special Tests (Optional):

  • Lightning impulse test
  • Temperature rise test
  • Sound level test
  1. Service Conditions
  • Installation altitude: ≤ 1000 m above sea level
  • Ambient temperature:
  • Maximum: +40°C
  • Minimum: −25°C (lower on request)
    • Relative humidity: ≤ 95%
  1. Applications
  • Utility distribution networks
  • Industrial plants
  • Commercial facilities
  • Renewable energy systems
  • Compact and pad-mounted substations
  1. Compliance Statement

The medium voltage oil-immersed transformer is designed, manufactured and tested in accordance with IEC 60076 standards and applicable international requirements.